D 50S - W Rectangular Bus Bar: Current Ratings
Size
I Bar
II Bars
III Bars
IIII Bars
(in)
50 c/s
50 c/s
50 c/s
50 c/s
.
D.C
A.C
D.C
A.C
D.C
A.C
D.C
A.C
1 x1/4
355
355
710
705
980
970
1120
1100
1 1/2 x1/4
520
520
1030
1020
1380
1350
1585
1535
21/2 x 1/4
670
670
1315
1290
1765
1705
2050
1940
3 x1/4
970
960
1805
1740
2440
2310
2860
2620
4 x1/4
1260
1235
2260
2140
3060
2800
3640
2300
5 x1/4
1545
1505
2700
2510
3660
3240
4410
3700
6 x 1/4
1840
1780
3130
2860
4290
3680
5250
4240
2 x1/4
840
830
1560
1500
2090
1970
2460
2260
3 x 3/8
1210
1180
2180
2050
2940
2660
3510
3030
4 x 3/8
1550
1495
2710
2480
3660
3150
4400
3560
5 x 3/8
1940
1860
3290
2930
4450
3660
5400
4200
6 x 3/8
2260
2120
3770
3340
5140
4080
6320
4680
8 x 3/8
2940
2750
4800
4150
6500
4900
8060
5740
3 x 1/2
1405
1355
2450
2240
3290
2830
4000
3240
4 x 1/2
1830
1740
3100
2720
4170
3360
5100
3900
5 x 1/2
2230
2080
3720
3120
5040
3900
6170
4550
6 x 1/2
2620
2420
4300
3500
5850
4400
7200
5100
8 x 1/2
3380
3060
5450
4450
7420
5300
9110
6150
10 x 1/2
4080
3640
6500
5000
8860
6000
10900
6850

Notes

  • Ratings for 50C rise over 35C ambient temperature instill but unconfined air.
  • For multiple-bar arrangements, the space between bars is equal to the bar thickness
  • A.C ratings are based on spacing at which proximity effect is negligible

COMPARISON OF REFRIGERANTS
Refrigerant
C.O.P
Relative efficiency
H.P / Ton
Evaporating press
Condensing press
Ideal
5.74
100
0.82
.
.
Ammonia
4.75
82.7
0.97
19.6
154.5
Carbon dioxide
2.59
45.1
1.83
316.8
1028.3
Freon - 12
4.69
81.6
1.01
11.8
93.2
 Methyl Chloride
4.62
80.5
1.02
6.5
80.0
Sulphur dioxide
4.74
82.5
0.99
2.9
51.8

Back